PVC Low Voltage

Product Datasheets and Approvals

PVC Low VoltagePrint summary for selected product(s)
Print
Compare two selected products
Compare
PVC Low Voltage 0.6/1.0kV Copper
BASEC
 Product Image
Datasheet
Approval
3D Model
Voltage Rating 600/1000 volts
Description PVC Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, PVC bedding, single core AWA 2 or more cores SWA, PVC sheath.
Operating Temperature -15degC to +90degC
Minimum Bending Radius 6x circular conductors
8x shaped conductors
Core Identification 1 core Bn or Be
2 core Bn, Be
3 core Bn, Bk,Gy
4 core Bn, Bk, Gy, Be
5 core Gn/Yw, Be, Bn, Bk, Gy
Multicore - white cores with black printed numbers
Sheath Colour Black
Manufacturing Standard BS 5467
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
PVC Low Voltage 1.9/3.3kV Copper
 Product Image
Datasheet
3D Model
Voltage Rating 1900/3300 volts
Description PVC Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, PVC bedding, single core AWA 2 or more cores SWA, PVC sheath.
Operating Temperature -15degC to +90degC
Minimum Bending Radius 6x circular conductors
8x shaped conductors
Core Identification 1 core Bn or Be
3 core Bn, Bk, Gy
Sheath Colour Black
Manufacturing Standard BS 5467
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC

product

Product Categories

Current Ratings

Navigation Key

  • Product Datasheet
  • Product Approval(s)
  • Product 3D Model
  • Compare two selected products
  • Print summary data for selected products

Helpful Hints

  • info

    Product detail can be viewed by clicking on the desired product title.

  • info

    When viewing a 3D cable model, use the mouse to control rotation. The names of component parts will be shown when hovering over the model.