2182/3/4Y (H03VVF)
 Product Image
Datasheet
3D Model
Voltage Rating 300/300 volts
Description PVC Light Duty Flexible Cords
Construction Plain copper conductor, PVC insulated two, three or four cores twisted together and PVC sheathed
Operating Temperature -15degC to +70degC
Minimum Bending Radius 3x
Core Identification 2 core Be, Bn
3 core Gn/Yw, Be, Bn
4 core Gn/Yw, Bn, Bk, Gy.
Lengths 50/100m
Sheath Colour White or black
Manufacturing Standard BS 6500:2000 Table 26
BS EN 50525-2-11 Table B1
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
2192Y (H03VVH2-F)
 Product Image
Datasheet
3D Model
Voltage Rating 300/300 volts
Description PVC Light Duty Flexible Cords (Flat)
Construction Plain copper conductors, PVC insulated, two cores laid flat and PVC sheathed.
Operating Temperature -15degC to +70degC
Minimum Bending Radius 3x
Core Identification Be and Bn
Lengths 50/100m
Sheath Colour White
Manufacturing Standard BS 6500:2000 Table 26
BS EN 50525-2-11 Table B1
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
3092/3/4Y (H05V2V2-F)
 Product Image
Datasheet
3D Model
Voltage Rating 300/500 volts
Description PVC Ordinary duty flexible cords (Heat Resisting). Heat resisting flexible cords for use in higher temperatures as a feed for portable tools, immersion heaters etc.
Construction Plain copper conductors, HRPVC insulated 2,3,4 cores twisted together and HRPVC sheath.
Operating Temperature -15degC to +90degC
Minimum Bending Radius 3x for fixed wiring
6x for flexing
Core Identification 2 core Be, Bn
3 core Gn/Yw, Be, Bn
4 core Gn/Yw, Bn, Bk, Gy
Lengths 50/100m
Sheath Colour White
Manufacturing Standard BS6500:2000 Table 29
BSEN50525-2-11 Table B2
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 50265
Special Notes Where a conductor operates at a temperature exceeding 70C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.
Min temperature for installation is +5degC
3182/3/4/5Y (H05VV-F)
 Product Image
Datasheet
3D Model
Voltage Rating 300/500 volts
Description PVC Ordinary duty flexible cords. General purpose flexible cords for feeds to portable tools and domestic appliances. Can be used indoors or outdoors where extreme temperatures are not expected. See special notes for alternative flexible cords for higher and lower temperature applications.
Construction Plain copper conductors, PVC insulated cores twisted together, PVC sheathed.
Operating Temperature -15degC to +70degC
Minimum Bending Radius 3x for fixed cable
6x for flexing.
Core Identification 2 core Be, Bn
3 core Gn/Yw, Be, Bn
4 core Gn/Yw, Bn, Bk, Gy
5 core Gn/Yw, Be, Bn, Bk, Gy
Lengths 50/100m
Sheath Colour White
Manufacturing Standard BS6500:2000 Table 27
BS EN 50525-2-11 Table B2
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 50265
Special Notes For higher temperature flex see Heat Resisting.
For low temperature flex see Arctic grade
Min temperature for installation is +5degC
3183A (Arctic Grade)
 Product Image
Datasheet
3D Model
Voltage Rating 300/500 volts
Description PVC Ordinary Duty Flexible Cords (Arctic Grade). These cords retain their flexibility at low temperatures, to -25C, and are therefore suitable for indoor and outdoor use to feed equipment such as temporary traffic lights and portable tools.
Construction Flexible plain copper conductors, low temperature PVC insulation, cores laid up, low temperature PVC sheath.
Operating Temperature -25degC to +70degC
Minimum Bending Radius 3x for fixed cable
6x for flexing.
Core Identification 3 core Gn/Yw, Be, Bn
Lengths 100m
Sheath Colour Blue or yellow
Manufacturing Standard BS6004 Table 6
BS7919:2001 Table 44
Fire Tests N/A
Emissions and
Flame Propagation
BS EN 50265

product

Product Categories

Current Ratings

Navigation Key

  • Product Datasheet
  • Product Approval(s)
  • Product 3D Model
  • Compare two selected products
  • Print summary data for selected products

Helpful Hints

  • info

    Product detail can be viewed by clicking on the desired product title.

  • info

    When viewing a 3D cable model, use the mouse to control rotation. The names of component parts will be shown when hovering over the model.