show/hide product data6491X
Close6491X
BASECProduct Image
Voltage Rating 450/750 volts
Description PVC Conduit Wiring. Primarily for use within conduit or trunking but may also be used where suitable protection against mechanical damage exists eg within light fittings, switchgear and control gear.
Construction Solid or stranded plain copper conductors, single core, PVC insulation
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x 1.5sq to 25sq 4x 35sq to 240sq, 6x 300 to 630sq
Core
Identification
Bn, Be, Bk, Gy, Gn/Yw, Yw*, Rd. Oe, Pk, Te, Vt, We
Lengths 100/500m 1.5 - 4.0 50/100/500m 6.0 - 25. Special Lengths available on request
Sheath Colour N/A
Manufacturing
Standard
BS6004 Table 4a
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes * yellow is a non harmonised colour. Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data6491B
Close6491B
BASECProduct Image
Voltage Rating 450/750 volts
Description Low Smoke Zero Halogen (LSZH) Conduit Wiring. For use in situations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment. Primarily for use within conduit or trunking but may also be used where suitable protection against mechanical damage exists eg within light fittings, switchgear and control gear.
Construction Stranded plain copper conductors, LSZH insulation
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
3x 1.5sq to 25sq 4x 35sq to 185sq 6x 240 to 630sq
Core
Identification
Bn, Be, Bk, Gy, Gn/Yw, Rd, We
Lengths 100/500m. Special lengths available on request
Sheath Colour N/A
Manufacturing
Standard
BS7211 Table 3a
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265 (IEC 60332) Flame Propagation
Special Notes Where a conductor operates at a temperature exceeding 70C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature. Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
 
Surface WiringPrint
Select
Product
Compare
show/hide product data6241Y
Close6241Y
BASECProduct Image
Voltage Rating 300/500 volts
Description PVC Surface Wiring. For use in light industrial and domestic applications where the risk of mechanical damage is low. It may be clipped direct to a surface, on a tray, in free air or can be embedded in plaster. It is suitable for use within conduit where there is a greater risk of mechanical damage.
Construction Solid plain copper conductors, single core, PVC insulated, core laid flat with a non insulated circuit protective conductor (cpc), PVC sheath.
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x
Core
Identification
Bn or Be
Lengths 100m
Sheath Colour Grey
Manufacturing
Standard
BS6004 Table 8
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data6242/3Y
Close6242/3Y
BASECProduct Image
Voltage Rating 300/500 volts
Description PVC Surface Wiring. For use in light industrial and domestic applications where the risk of mechanical damage is low. It may be clipped direct to a surface, on a tray, in free air or can be embedded in plaster. It is suitable for use within conduit where there is a greater risk of mechanical damage.
Construction Plain copper conductors, PVC insulated, cores laid flat with a non insulated circuit protective concuctor (cpc), PVC sheath.
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x 1 to 1.5sq 2 core, 4x 2.5 to 16sq 2 core, 4x 1 to 6sq 3 core, 6x 10 to 16sq 3 core
Core
Identification
2 core Bn, Be, 3 core Bn, Bk, Gy.
Lengths 50/100/500m 1.5 - 6.0 50/100m 10.0 -16.0.
Sheath Colour Grey
Manufacturing
Standard
BS6004 Table 8 IS201-4 Table 1
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
Approval2
3D Cable Model 3D
show/hide product data6242/3B
Close6242/3B
BASECProduct Image
Voltage Rating 300/500 volts
Description Low Smoke Zero Halogen Surface Wiring. For use in situations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment. For use in light industrial and domestic applications where the risk of mechanical damage is low. It may be clipped direct to a surface, on a tray, in free air or can be embedded in plaster. It is suitable for use within conduit where there is a greater risk of mechanical damage.
Construction Plain copper conductors, XLPE insulation, cores laid flat with a non insulated circuit protective conductor (cpc), LSZH sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
3x 1sqmm to 2.5sq 2 core 4x 4sqmm to16sqmm 2 core 4x 1sqmm to 10sqmm 3core 6x 16sq 3 core.
Core
Identification
2 core Bn, Be, 3 core Bn, Bk, Gy.
Lengths 100/500m 1.5 - 6.0 100m 10.0 - 16.0 100m 6243B 1.5
Sheath Colour White
Manufacturing
Standard
BS7211 Table 7
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265 (IEC 60332) Flame Propagation
Special Notes Where a conductor operates at a temperature exceeding 70C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature. Min temperature for installation is +5degC.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data6181Y-H
Close6181Y-H
BASECProduct Image
Voltage Rating 300/500 volts
Description PVC Surface Wiring. Often referred to as 'double insulated cable'. For use in light industrial and domestic applications where the risk of mechanical damage is low. They may be clipped direct to a surface, on a tray, in free air or can be embedded in plaster. It is suitable for use within conduit where there is a greater risk of mechanical damage.
Construction Plain copper conductor, single core, PVC insulated and PVC sheathed
Operating
Temperature
-15degC to + 70degC
Minimum
Bending Radius
3x 1.0sq to 16sq. 4x 25sq to 35sq
Core
Identification
Bn or Be
Lengths 100m 1.0 1.5 50/100m 16 - 35. Special lengths available on request.
Sheath Colour Grey
Manufacturing
Standard
BS6004 Table 7
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data6181XLPE
Close6181XLPE
Product Image
Voltage Rating 600/1000 volts
Description PVC Surface Wiring. These are rated at 90C rather than 70C for 6181Y PVC insulated cables and therefore have a higher current carrying capacity for an equivalent size of cable. For use in light industrial and domestic applications where the risk of mechanical damage is low. They may be clipped direct to a surface, on a tray, in free air or can be embedded in plaster. It is suitable for use within conduit where there is a greater risk of mechanical damage.
Construction Stranded plain copper conductors, XLPE insulation, PVC sheath
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
4x 50sqmm to 185sqmm 6x 240sqmm to 1000sqmm
Core
Identification
Bn or Be
Sheath Colour Black
Manufacturing
Standard
BS7889 Table 3
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Where a conductor operates at a temperature exceeding 70C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature. Min temperature for installation is +5gegC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data6192/3Y
Close6192/3Y
BASECProduct Image
Voltage Rating 300/500 volts
Description PVC Surface Wiring
Construction Plain copper conductors, PVC insulated cores laid flat and PVC sheathed.
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
4x
Core
Identification
2 core Bn, Be, 3 core Bn, Bk, Gy.
Sheath Colour Grey
Manufacturing
Standard
BS6004 Table 7
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
 
ProtecPrint
Select
Product
Compare
show/hide product dataProtec
CloseProtec
ERAProduct Image
Voltage Rating 600/1000 volts
Description Screened cable for use in walls, partitions and building voids where there is a risk of damage or penetration from nails, screw fixings etc. Based upon the material and constructional requirements of BS8436 and is suitable for use at voltages up to and including 600/1000V.
Construction Solid or stranded plain coppper conductors, XLPE insulation, full size earth, aluminium tubed screen, LSZH sheath.
Operating
Temperature
-25degC to +90degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
2 core Bn, Be 3 core Bn, Blk, Gy 4 core Bn, Blk, Gy, Be
Lengths 100m
Sheath Colour White, other colours available
Manufacturing
Standard
BS8436
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is +5degC. Once installed and fixed can operate to -25degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
 
PVC Flexible CordsPrint
Select
Product
Compare
show/hide product data2182/3/4Y
Close2182/3/4Y
BASECProduct Image
Voltage Rating 300/300 volts
Description PVC Light Duty Flexible Cords
Construction Plain copper conductor, PVC insulated two, three or four cores twisted together and PVC sheathed
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x
Core
Identification
2 core Be, Bn 3 core Gn/Yw, Be, Bn, 4 core Gn/Yw, Bn, Bk, Gy.
Lengths 50/100m
Sheath Colour White or black
Manufacturing
Standard
BS6500 Table 26
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data2192Y
Close2192Y
BASECProduct Image
Voltage Rating 300/300 volts
Description PVC Light Duty Flexible Cords (Flat)
Construction Plain copper conductors, PVC insulated, two cores laid flat and PVC sheathed.
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x
Core
Identification
Be and Bn
Lengths 50/100m
Sheath Colour White
Manufacturing
Standard
BS6500 Table 26
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data3092/3/4Y
Close3092/3/4Y
Product Image
Voltage Rating 300/500 volts
Description PVC Ordinary duty flexible cords (Heat Resisting). Heat resisting flexible cords for use in higher temperatures as a feed for portable tools, immersion heaters etc.
Construction Plain copper conductors, HRPVC insulated 2,3,4 cores twisted together and HRPVC sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
3x for fixed wiring 6x for flexing
Core
Identification
2 core Be, Bn 3 core Gn/Yw, Be, Bn 4 core Gn/Yw, Bn, Bk, Gy
Lengths 50/100m
Sheath Colour White
Manufacturing
Standard
BS6500 Table 29
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes Where a conductor operates at a temperature exceeding 70C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature. Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data3182/3/4/5Y
Close3182/3/4/5Y
BASECProduct Image
Voltage Rating 300/500 volts
Description PVC Ordinary duty flexible cords. General purpose flexible cords for feeds to portable tools and domestic appliances. Can be used indoors or outdoors where extreme temperatures are not expected. See special notes for alternative flexible cords for higher and lower temperature applications.
Construction Plain copper conductors, PVC insulated cores twisted together, PVC sheathed.
Operating
Temperature
-15degC to +70degC
Minimum
Bending Radius
3x for fixed cable 6x for flexing.
Core
Identification
2 core Be, Bn 3 core Gn/Yw, Be, Bn 4 core Gn/Yw, Bn, Bk, Gy 5 core Gn/Yw, Be, Bn, Bk, Gy
Lengths 50/100m
Sheath Colour White
Manufacturing
Standard
BS6500 Table 27
Code of Practice/
Guide to Use
BS 7540
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Special Notes For higher temperature flex see Heat Resisting. For low temperature flex see Arctic grade Min temperature for installation is +5degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product dataArctic Grade
CloseArctic Grade
Product Image
Voltage Rating 300/500 volts
Description PVC Ordinary Duty Flexible Cords (Arctic Grade). These cords retain their flexibility at low temperatures, to -25C, and are therefore suitable for indoor and outdoor use to feed equipment such as temporary traffic lights and portable tools.
Construction Flexible plain copper conductors, low temperature PVC insulation, cores laid up, low temperature PVC sheath.
Operating
Temperature
-25degC to +70degC
Minimum
Bending Radius
3x for fixed cable 6x for flexing.
Core
Identification
3 core Gn/Yw, Be, Bn
Lengths 100m
Sheath Colour Blue or yellow
Manufacturing
Standard
BS7919 Table 44
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50265
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
 
Tri-Rated CablesPrint
Select
Product
Compare
show/hide product dataTri-Rated
CloseTri-Rated
Product Image
Voltage Rating 600/1000 volts
Description Tri rated panel wiring
Construction Flexible plain copper conductoor, HRPVC insullation
Operating
Temperature
+5degC to +90degC
Minimum
Bending Radius
3x for fixed cable 6x for flexing.
Core
Identification
Bk, We, Rd, Bn, Be, Yw, Gn/Yw, Gy.
Lengths 100m
Sheath Colour N/A
Manufacturing
Standard
BS6231 Type CK Table 4a. UL758 CSA C22.2 No 127-95
Fire Tests N/A
Emissions
and Flame
Propagation
BS 4066-1 CSA C22.2 FT1 UL 1581 VW1
Special Notes Cables 150sqmm and above are bi-rated.
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
 
Mineral InsulatedPrint
Select
Product
Compare
show/hide product dataLight Duty (Bare)
CloseLight Duty (Bare)
SIRALPCBProduct Image
Voltage Rating 500 volts
Description Mineral insulated cable is the ultimate fire performance cable. It guarantees the integrity of data transmission and security of both power and control circuits. Exceeding the requirements of BS8519 & BS5839-1 it provides curcuit integrity during and after fires at temperatures up to 950 degC. It exceeds the enhanced grade as defined by BS5839-2 26.2e. It is the only universal cable that satisfies all Category 1, 2 & 3 Power requirements & all Category 1, 2 &3 Control requirements defined by BS8519.
Construction Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath.
Operating
Temperature
-10degC to +250degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
Coloured sleeving available
Lengths 100/500m. Special lengths available on request.
Sheath Colour N/A
Manufacturing
Standard
BS EN 60702-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 & power applications see special notes)
Fire Tests BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z BS 8491
Emissions
and Flame
Propagation
In its bare form there are no emmissions
Special Notes 1 Testing at AEI Cables has cnfirmed that the cable complies with BS8519 Category 3 Control & Category 1, 2 & 3 Power ( clause 11, note 2 for cables < 20mm OD) 2 Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataHeavy Duty (Bare)
CloseHeavy Duty (Bare)
SIRALPCBProduct Image
Voltage Rating 750 volts
Description Mineral insulated cable is the ultimate fire performance cable. It guarantees the integrity of data transmission and security of both power and control circuits. Exceeding the requirements of BS8519 & BS5839-1 it provides curcuit integrity during and after fires at temperatures up to 950 degC. It exceeds the enhanced grade as defined by BS5839-2 26.2e. It is the only universal cable that satisfies all Category 1, 2 & 3 Power requirements & all Category 1, 2 &3 Control requirements defined by BS8519.
Construction Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath.
Operating
Temperature
-10degC to +250degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
Coloured sleeving available
Lengths Cables available in nominal lengths.
Sheath Colour N/A
Manufacturing
Standard
BS EN 60702-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 & power applications see special notes)
Fire Tests BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z BS 8491
Emissions
and Flame
Propagation
In its bare form there are no emmissions
Special Notes 1 Testing at AEI Cables has cnfirmed that the cable complies with BS8519 Category 3 Control & Category 1, 2 & 3 Power ( clause 11, note 2 for cables < 20mm OD) 2 Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataLight Duty (LSZH)
CloseLight Duty (LSZH)
SIRALPCBProduct Image
Voltage Rating 500 volts
Description Mineral insulated cable is the ultimate fire performance cable. It guarantees the integrity of data transmission and security of both power and control circuits. Exceeding the requirements of BS8519 & BS5839-1 it provides curcuit integrity during and after fires at temperatures up to 950 degC. It exceeds the enhanced grade as defined by BS5839-2 26.2e. It is the only universal cable that satisfies all Category 1, 2 & 3 Power requirements & all Category 1, 2 &3 Control requirements defined by BS8519.
Construction Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath and thermoplastic LSZH sheath.
Operating
Temperature
-10degC to +250degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
Coloured sleeving available
Lengths 100/500m. Special lengths available on request.
Sheath Colour Red, White or Orange. Other colours available.
Manufacturing
Standard
BS EN 60702-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 & power applications see special notes)
Fire Tests BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z BS 8491
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes 1 Testing at AEI Cables has cnfirmed that the cable complies with BS8519 Category 3 Control & Category 1, 2 & 3 Power ( clause 11, note 2 for cables < 20mm OD) 2 Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataHeavy Duty (LSZH)
CloseHeavy Duty (LSZH)
SIRALPCBProduct Image
Voltage Rating 750 volts
Description Mineral insulated cable is the ultimate fire performance cable. It guarantees the integrity of data transmission and security of both power and control circuits. Exceeding the requirements of BS8519 & BS5839-1 it provides curcuit integrity during and after fires at temperatures up to 950 degC. It exceeds the enhanced grade as defined by BS5839-2 26.2e. It is the only universal cable that satisfies all Category 1, 2 & 3 Power requirements & all Category 1, 2 &3 Control requirements defined by BS8519.
Construction Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath and thermoplastic LSZH sheath.
Operating
Temperature
-10degC to +250degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
Coloured sleeving available
Lengths Cables available in nominal lengths.
Sheath Colour Red, White or Orange. Other colours available.
Manufacturing
Standard
BS EN 60702-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 & power applications see special notes)
Fire Tests BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z BS 8491
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes 1 Testing at AEI Cables has cnfirmed that the cable complies with BS8519 Category 3 Control & Category 1, 2 & 3 Power ( clause 11, note 2 for cables < 20mm OD) 2 Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataClip Sizes
CloseClip Sizes
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model N/A
show/hide product dataAccessories
CloseAccessories
Manufacturing
Standard
BS EN 60702-2
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model N/A
 
FiretecPrint
Select
Product
Compare
show/hide product dataFiretec Single
CloseFiretec Single
LPCBProduct Image
Voltage Rating 600/1000 volts
Description Firetec Singlecore is designed to be installed in metal conduit. For use in alarm and emergency lighting circuits for new installations or upgrading existing conduit systems to fire performance standards. Elastomeric insulation gives high mechanical strength, excellent flexibility and resistance to abrasion.
Construction Stranded plain annealed copper conductors. Mica/glass fire barrier tape. Elastomeric LSZH outer sheath.
Operating
Temperature
-10degC to +90degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
Bn, Bk, Gy, Be, Rd, Oe, Yw, Gn/Yw. Other colours available on request.
Lengths 100/500m. Special lengths available on request.
Sheath Colour N/A
Manufacturing
Standard
BS7211 (Generally to , fire resistant)
Code of Practice/
Guide to Use
N/A
Fire Tests BS 6387 C, W, Z and IEC 60331-21 when tested in a steel conduit at a temperature of 950şC and an increased voltage of 600/1000volts.
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataFiretec Standard
CloseFiretec Standard
BASECLPCBProduct Image
Voltage Rating 300/500 volts
Description Firetec Standard cable is suitable for fire alarm systems and emergency lighting circuits. It meets the standard grade of BS 5839 26.2d & Category 1 Control as defined by BS8519.
Construction Solid or stranded plain annealed copper conductors. Tinned annealed copper full size CPC. Aluminium/polyester laminated tape screen. LSZH insulation and outer sheath.
Operating
Temperature
-10degC to +90degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
2 core Bn, Be 3 core Bn, Bk, Gy 4 core Bn, Bk, Gy, Be
Lengths 100/500m. Special lengths available on request.
Sheath Colour Red or White. Other colours available.
Manufacturing
Standard
BS 7629-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2d Standard BS 5266 BS 8519 Category 1 Control
Fire Tests BS 8434-1 BS EN 50200 PH30, PH60 BS 6387 C W & Z
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataFiretec Enhanced
CloseFiretec Enhanced
BASECLPCBProduct Image
Voltage Rating 300/500 volts
Description Firetec Enhanced cable is suitable for fire alarm systems, emergency lighting circuits & Category 1, 2 & 3 Control circuits as defined in BS8519. The mica glass tape is applied directly over the conductor to ensure the best possible enhanced fire performance. It meets enhanced grade as defined by BS5839-1 26.2e.
Construction Solid or stranded plain annealed copper conductors. Tinned annealed copper full size CPC. Mica/glass fire barrier tape. Aluminium/polyester laminated tape screen. LSZH insulation and outer sheath.
Operating
Temperature
-10degC to +90degC
Minimum
Bending Radius
6 x overall diameter
Core
Identification
2 core Bn, Be 3 core Bn, Bk, Gy 4 core Bn, Bk, Gy, Be
Lengths 100/500m. Special lengths available on request.
Sheath Colour Red or White. Other colours available.
Manufacturing
Standard
BS 7629-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced BS 5266 BS 8519 Category 1 & 2 Control (for Category 3 control see special notes)
Fire Tests BS 8434-2 BS EN 50200 PH30, PH60, PH120 BS 6387 C W & Z
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes 1 Testing at AEI Cables has confirmed that the cable complies with BS8519 Category 3 Control. 2 Methods of cable support should withstand a similar temperature and duration to that of the cable.
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product dataFiretec Armoured
CloseFiretec Armoured
BASECLPCBProduct Image
Voltage Rating 600/1000 volts
Description Firetec Armoured cable is fire resistant and is suitable for use in fixed installations for power circuits, fire alarm systems & emergency lighting systems. This cable is robust, flexible and suitable for use inside and outside buildings.
Construction Stranded plain annealed copper conductors. Mica/glass fire barrier tape. Cross linked polyethylene insulation (XLPE). LSZH bedding, steel wire armouring and LSZH outer sheath.
Operating
Temperature
-10degC to +90degC
Minimum
Bending Radius
6 x overall diameter 8 x for 25mm˛ and above
Core
Identification
2 core Bn, Be 3 core Bn, Bk, Gy 4 core Bn, Bk, Gy, Be Multicore - white cores with black printed numbers
Lengths Cut lengths on request.
Sheath Colour Black
Manufacturing
Standard
BS 7846
Code of Practice/
Guide to Use
BS5266 See special notes below
Fire Tests BS 6387 C W & Z BS 7846 F2
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes 1. *Old core colours available. 2c Rd, Blk. 3c Rd, Yw, Be. 4c Rd, Yw, Be, Blk. 2. This cable can be supplied without steel wire armour for situations wher sufficient mechanical protection already exists and where a smaller, lighter, more flexible cable would be preferred. Simply request details of our Firetec Unarmoured range of cables. Fire resistant to BS 6387 C W & Z, LSZH material used throughout, LPCB approved. 3. Methods of cable support should withstand a similar temperature and duration to that of the cable. 4. Testing at AEI has confirmed that the cable complies with BS8519 Category 1, 2 & 3 Control and meets the requirements for an enhanced grade of cable to BS5839 26.2e.
Product Datasheet Datasheet
Product Approval(s) Approval1
Approval2
Approval3
3D Cable Model 3D
 
PVC Low VoltagePrint
Select
Product
Compare
show/hide product data0.6/1.0kV Copper
Close0.6/1.0kV Copper
BASECProduct Image
Voltage Rating 600/1000 volts
Description PVC Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, PVC bedding, single core AWA 2 or more cores SWA, PVC sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
6x circular conductors 8x shaped conductors
Core
Identification
1 core Bn or Be 2 core Bn, Be 3 core Bn, Bk,Gy 4 core Bn, Bk, Gy, Be 5 core Gn/Yw, Be, Bn, Bk, Gy Multicore - white cores with black printed numbers
Sheath Colour Black
Manufacturing
Standard
BS 5467
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data1.9/3.3kV Copper
Close1.9/3.3kV Copper
Product Image
Voltage Rating 1900/3300 volts
Description PVC Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, PVC bedding, single core AWA 2 or more cores SWA, PVC sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
6x circular conductors 8x shaped conductors
Core
Identification
1 core Bn or Be 3 core Bn, Bk, Gy
Sheath Colour Black
Manufacturing
Standard
BS 5467
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
 
LSZH Low VoltagePrint
Select
Product
Compare
show/hide product data0.6/1.0kV Copper
Close0.6/1.0kV Copper
BASECProduct Image
Voltage Rating 600/1000 volts
Description LSZH Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. For use in situations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, LSZH bedding, single core AWA 2 or more cores SWA, LSZH sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
6x circular conductors 8x shaped conductors
Core
Identification
1 core Bn or Be 2 core Bn, Be 3 core Bn, Blk, Gy 4 core Bn, Blk, Gy, Be 5 core Gn/Yw, Be, Bn, Bk, Gy Multicore - white cores with black printed numbers
Sheath Colour Black
Manufacturing
Standard
BS 6724
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) Approval1
3D Cable Model 3D
show/hide product data1.9/3.3kV Copper
Close1.9/3.3kV Copper
Product Image
Voltage Rating 1900/3300 volts
Description LSZH Armoured cables for use in fixed installations in industrial areas, buildings and similar applications. For use in situations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment. They may be installed in air, on trays, clipped direct or be buried in the ground.
Construction Stranded plain copper conductors, XLPE insulation, cores laid up, LSZH bedding, single core AWA 2 or more cores SWA, LSZH sheath.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
6x circular conductors 8x shaped conductors
Core
Identification
1 core Bn or Be 3 core Bn, Bk, Gy
Sheath Colour Black
Manufacturing
Standard
BS 6724
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
 
PVC Medium VoltagePrint
Select
Product
Compare
show/hide product data3.8/6.6kV Copper
Close3.8/6.6kV Copper
Product Image
Voltage Rating 3800/6600 volts
Description PVC armoured power cables for use in fixed installations
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P5.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS6622
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data6.35/11kV Copper
Close6.35/11kV Copper
Product Image
Voltage Rating 6350/11000 volts
Description PVC armoured power cables for use in fixed installations
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P6.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS6622
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data8.7/15kV Copper
Close8.7/15kV Copper
Product Image
Voltage Rating 8700/15000 volts
Description PVC armoured power cables for use in fixed installations
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P7.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS6622
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data12.7/22kV Copper
Close12.7/22kV Copper
Product Image
Voltage Rating 12700/22000 volts
Description PVC armoured power cables for use in fixed installations
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P8.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS6622
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data19/33kV Copper
Close19/33kV Copper
Product Image
Voltage Rating 19000/33000 volts
Description PVC armoured power cables for use in fixed installations
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P9.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS6622
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 60332
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
 
LSZH Medium VoltagePrint
Select
Product
Compare
show/hide product data3.8/6.6kV Copper
Close3.8/6.6kV Copper
Product Image
Voltage Rating 3800/6600 volts
Description LSZH armoured power cables for use in fixed installations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment.
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P10.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS7835
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data6.35/11kV Copper
Close6.35/11kV Copper
Product Image
Voltage Rating 6350/11000 volts
Description LSZH armoured power cables for use in fixed installations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment.
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P11.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS7835
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data8.7/15kV Copper
Close8.7/15kV Copper
Product Image
Voltage Rating 8700/15000 volts
Description LSZH armoured power cables for use in fixed installations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment.
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P12.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS7835
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data12.7/22kV Copper
Close12.7/22kV Copper
Product Image
Voltage Rating 12700/22000 volts
Description LSZH armoured power cables for use in fixed installations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment.
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P13.
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS7835
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D
show/hide product data19/33kV Copper
Close19/33kV Copper
Product Image
Voltage Rating 19000/33000 volts
Description LSZH armoured power cables for use in fixed installations where smoke and acid gas emission from fire affected cables would be hazardous to people and equipment.
Construction Core construction - Stranded plain copper conductors, SC conductor screen, XLPE insulation, SC insulation screen, plain copper tape. For optional cable constructions refer Technical Data Sheet P14
Operating
Temperature
-15degC to +90degC
Minimum
Bending Radius
15x for single core 12x for 3 core
Core
Identification
3 core Rd, Yw, Be or by numbers
Sheath Colour Black or Red
Manufacturing
Standard
BS7835
Fire Tests N/A
Emissions
and Flame
Propagation
BS EN 50267 (IEC 60754) Acid Gas Emission BS EN 50268 (IEC 61034) Smoke Emission BS EN 50265,50266 (IEC 60332) Flame Propagation
Special Notes Minimum temperature for installation purposes is 0degC
Product Datasheet Datasheet
Product Approval(s) N/A
3D Cable Model 3D

Compare Selected Products

Print Selected Product Data
navigation tips
Product detail can be viewed by clicking on the desired product type.

Two products can be compared by ticking their boxes and then clicking here or on the 'Compare' link below the list.

After selecting one or more products to be printed, click here or on the 'Print' link below the list.

When viewing a 3D cable model, use the mouse to control rotation. The names of component parts will be shown when hovering over the model.